PRODUCT INFORMATION

GLT series gas burners (100,000~1,200,000 kcal, medium to large size, capable of two-stage ignition)

Product Information

Medium to large-scale gas burners with a capacity of 100,000 to 1,200,000 kcal/kg | Suitable for two-stage (high-low) fire control, medium-pressure gas supply, and LPG/LNG, with a wide range of firepower adjustment. GLT series gas burners (100,000~1,200,000 kcal, medium to large size, capable of two-stage ignition)

A new option for medium and large-scale gas combustion: GLT with 10 to 1.2 million kcal/kg capacity and two-stage ignition, offering flexible heat output and fuel efficiency.

中大型場域,需要能調節火力的瓦斯燃燒機

中大型熱能設備的負載常有變化,若只能全火運轉,容易耗燃料、溫度波動大。GLT 系列瓦斯燃燒機熱功率涵蓋 10~120 萬大卡(約 116~1395 kW),可二段火(High-Low)控制,依負載切換火力,兼顧火力與效率。

 

GLT 系列的運作機制

GLT 系列可採二段火(High-Low)控制,在低火與高火兩段間依負載切換,比單純開關火更省燃料、溫度更穩定。供氣採中壓系統,管線較小、成本較低、施工容易;適用 LPG 桶裝瓦斯與 LNG 天然氣,無需變更既有設備。

 

GLT 系列的設計與安全特色

可搭配 UV 紫外線火焰監測控制器,火焰異常時自動警報並遮斷電源與瓦斯。GLT 涵蓋中大型火力並支援二段火調節,適合負載有變化、重視燃料效率的中大型場域。整機為日本 Olympia 原裝。

 

瓦斯燃燒機怎麼選(依熱功率)

Olympia 瓦斯燃燒機依熱功率級距分為多個系列,依製程熱需求選用:

系列 熱功率級距 適合
GLT(本頁) 10~120 萬大卡 中大型、可二段火
AG 5~300 萬大卡 中型至大型工業
GOM (N) 3~40 萬大卡 中小型、性價比
ATS TG-30GA 30 萬大卡 中型場域

更多見 Olympia Brand Page;可搭配 燃燒控制配件 使用。

 

Frequently Asked Questions (FAQ)

GLT 系列涵蓋多大火力? 10~120 萬大卡(約 116~1395 kW),屬中大型級距。

「二段火(High-Low)」有什麼好處? 可在低火與高火兩段間依負載切換,比單純開關火更省燃料、溫度更穩定。

GLT 和 AG、GOM 怎麼選? 依熱功率與控制需求:GOM 3~40 萬、GLT 10~120 萬(可二段火)、AG 5~300 萬(火力最大)。

LPG 和 LNG 都能用嗎? 可以,適用 LPG 桶裝瓦斯與 LNG 天然氣,無需變更既有設備。

中大型瓦斯燃燒新選擇,GLT 10到120萬大卡可二段火,火力收放自如又省燃料產品規格

Burning capacity (kcal/h X 1000) 400
detect probe
way to control two-stage
power supply Voltage V: 220/380 Phase: 3
Motor(KW) 0.40
Gas inlet size 25A

 

中大型瓦斯燃燒新選擇,GLT 10到120萬大卡可二段火,火力收放自如又省燃料尺寸圖

 

Burning capacity (kcal/h X 1000) 500
detect probe
way to control two-stage
power supply Voltage V: 220/380 Phase: 3
Motor(KW) 0.75
Gas inlet size LPG: 25A LNG: 2A

 

中大型瓦斯燃燒新選擇,GLT 10到120萬大卡可二段火,火力收放自如又省燃料尺寸圖

 

Burning capacity (kcal/h X 1000) 600
detect probe
way to control two-stage
power supply Voltage V: 220/380 Phase: 3
Motor(KW) 1
Gas inlet size LPG: 32A LNG: 40A

 

中大型瓦斯燃燒新選擇,GLT 10到120萬大卡可二段火,火力收放自如又省燃料尺寸圖

 

Burning capacity (kcal/h X 1000) 800
detect UV
way to control two-stage
power supply Voltage V: 220/380 Phase: 3
Motor(KW) 1.50
Gas inlet size LPG: 40A LNG: 50A

 

中大型瓦斯燃燒新選擇,GLT 10到120萬大卡可二段火,火力收放自如又省燃料尺寸圖

 

Burning capacity (kcal/h X 1000) 1200
detect UV
way to control two-stage
power supply Voltage V: 220/380 Phase: 3
Motor(KW) 2.20
Gas inlet size LPG: 40A LNG: 50A

 

中大型瓦斯燃燒新選擇,GLT 10到120萬大卡可二段火,火力收放自如又省燃料尺寸圖

 

fault state reason countermeasures
all do not move 1. No power supply
2. The fuse is blown
3. Motor overload
4. Motor switch failure
1. Check the total power
2. Check the control circuit for short circuit
3. Check whether the motor is faulty or replace it
4. Replace the switch
The motor will spin (but not fire) 1. Dirty ignition stick
2. The ignition rod is in contact with the burner
3. No ignition sound and sparks
4. The air pressure switch is set too high
1. Clean up
2. Adjustment
3. Check the ignition wire, electrode rod, ignition transformer or controller chassis feet
4. Adjustment
Lights up but goes out after a few seconds 1. Dirty electric eyes
2. The sensor rod is in contact with the flame
3. Insufficient gas pressure
4. Sensing rod wear
5. The feet 13 and 14 of the controller chassis are too open
1. Clean up
2. Adjustment
3. Adjustment
4. Replacement
5. Adjust the clamping
abnormal flameout 1. There is ignition but no ignition
2. Electric eye or sensor rod failure
1. The wind pressure is too large, adjust it down, the solenoid valve is faulty (updated), and there is no gas
2. Update the sensor or sensor stick