瓦斯燃燒機若採低壓供氣,減壓器隔膜有爆炸風險;火力調整範圍不足,也難以對應不同製程需求。ATS TG-30GA 以中壓供氣系統與寬廣的火力調整,兼顧安全與彈性,熱功率達 30 萬大卡(約 349 kW)。
TG-30GA 採中壓供氣系統,避免低壓減壓器隔膜爆炸的風險;供氣管線較小、建置成本較低、施工容易,且火力調整範圍廣。搭配特殊風門控制器提升燃燒效率,並提供多種噴嘴設計對應不同需求。本機適用 LPG 桶裝瓦斯與 LNG 天然氣,無需變更既有設備即可切換。
可搭配原廠自行開發的火焰警報控制器,以 UV 紫外線電眼監測火焰狀態;一旦偵測到異常火焰,自動發出警報並遮斷電源與瓦斯,達到防止火災、節能與安全的效果。整機採機械式附屬件、長壽命、高安全性設計。
「30 萬大卡」是多大? 約等於 349 kW 的熱功率,屬中型瓦斯燃燒機。
中壓供氣有什麼好處? 避免低壓減壓器隔膜爆炸風險,供氣管線較小、成本較低、施工容易,火力調整範圍也較廣。
LPG 和 LNG 都能用嗎? 可以,TG-30GA 適用 LPG 桶裝瓦斯與 LNG 天然氣,無需變更既有設備。
火焰異常會怎樣? 搭配 UV 火焰監測控制器時,異常火焰會自動警報並遮斷電源與瓦斯。
| Burning capacity (kcal/h X 1000) | 300 |
| detect | probe |
| way to control | two-stage |
| power supply | Voltage V: 220/380 Phase: 3 |
| Motor(KW) | 0.40 |
| Gas inlet size | 25A |
|
| Burning capacity (kcal/h X 1000) | 100 |
| detect | probe |
| way to control | one paragraph |
| power supply | Voltage V: 220/220 Phase: 1 |
| Motor(KW) | 0.15 |
| Gas inlet size | 20A |
|
| Burning capacity (kcal/h X 1000) | 200 |
| detect | probe |
| way to control | one paragraph |
| power supply | Voltage V: 220/220 Phase: 1 |
| Motor(KW) | 0.25 |
| Gas inlet size | 20A |
|
| Burning capacity (kcal/h X 1000) | 300 |
| detect | probe |
| way to control | one paragraph |
| power supply | Voltage V: 220/380 Phase: 3 |
| Motor(KW) | 0.40 |
| Gas inlet size | 25A |
|
| Burning capacity (kcal/h X 1000) | 400 |
| detect | probe |
| way to control | one paragraph |
| power supply | Voltage V: 220/380 Phase: 3 |
| Motor(KW) | 0.40 |
| Gas inlet size | LPG: 25A LNG: 40A |
|
| fault state | reason | countermeasures |
|---|---|---|
| all do not move | 1. No power supply 2. The fuse is blown 3. Motor overload 4. Motor switch failure |
1. Check the total power 2. Check the control circuit for short circuit 3. Check whether the motor is faulty or replace it 4. Replace the switch |
| The motor will spin (but not fire) | 1. Dirty ignition stick 2. The ignition rod is in contact with the burner 3. No ignition sound and sparks 4. The air pressure switch is set too high |
1. Clean up 2. Adjustment 3. Check the ignition wire, electrode rod, ignition transformer or controller chassis feet 4. Adjustment |
| Lights up but goes out after a few seconds | 1. Dirty electric eyes 2. The sensor rod is in contact with the flame 3. Insufficient gas pressure 4. Sensing rod wear 5. The feet 13 and 14 of the controller chassis are too open |
1. Clean up 2. Adjustment 3. Adjustment 4. Replacement 5. Adjust the clamping |
| abnormal flameout | 1. There is ignition but no ignition 2. Electric eye or sensor rod failure |
1. The wind pressure is too large, adjust it down, the solenoid valve is faulty (updated), and there is no gas 2. Update the sensor or sensor stick |